...4 CONFIGURATION
4.6 Set Up Remote Set Point Page
Information.
•
This page is omitted if Remote set point is not selected at Second Set Point Type in Set
Points Page – see Section 4.2.
•
Universal Input.
SEtUP
rSPt
INtYP2
MVLt
MAMP
VOLt
ohM
tCPL
rtd
LNtYP2
NONE
tC-K
tC-r
tC-S
tC-t
tC-J
tC-L
tC-E
tC-b
tC-N
rtd
SQrt
3 2
5 2
L–UNt2
dEG C
NONE
SQrt
LIN–HI
3 2
I000
5 2
20
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Page Header – Set Up Remote Set Point Input.
Remote Set Point Input Type
Select the input type required:
–
MVLt
–
MAMP
–
VOLt
–
ohM
–
tCPL
–
rtd
*For thermocouple applications using an external fixed
cold junction, select millivolt input type.
Remote Set Point Linearizer Type
Select the linearizer type required:
–
NONE
–
tC-K
tC-r
–
–
tC-S
–
tC-t
tC-J
–
tC-L
–
tC-E
–
–
tC-b
–
tC-N
–
rtd
–
SQrt
–
3/2
–
5/2
Linearizer Units
Select the temperature units required, °C or °F.
Linearizer Full Scale
Set the range maximum temperature in °C or °F as
selected at
Linearizer Units
in Table 4.1. If limits are exceeded,
overrange) is displayed in the
5.1a of the Operating Guide .
Continue on next page.
Millivot (≤2000mV)
Current
Voltage
Resistance
Thermocouple*
Resistance thermometer
No linearizer
Type K thermocouple
Type R thermocouple
Type S thermocouple
Type T thermocouple
Type J thermocouple
Type L thermocouple
Type E thermocouple
Type B thermocouple
Type N thermocouple
Resistance thermometer
Square root
x
3/2
5/2
x
above, within the limits detailed
LIN–Or
Operating Page
(linearizer
– see Table