2.2.8

Ramp-function generator

Description
The ramp-function generator is used to limit acceleration in the event of abrupt set-
point changes, which helps prevent load surges throughout the drive train. The
ramp-up time p1120[D] and ramp-down time p1121[D] can be used to set an acce-
leration ramp and a deceleration ramp independently of each other. This allows a
controlled transition to be made in the event of setpoint changes.
The maximum speed p1082[D] is used as a reference value for calculating the
ramps from the ramp-up and ramp-down times. A special adjustable ramp can be
set via p1135 for fast stop (OFF3), e.g. for rapid controlled deceleration when an
emergency stop button is pressed.
There are two types of ramp-function generator:
S Simple ramp-function generator with
– Acceleration and deceleration ramps
– Ramp for fast stop (OFF3)
– Tracking can be selected via a binector input
– Setting values for the ramp-function generator
S Extended ramp-function generator with
– Initial and final rounding off
Note
The ramp-function generator cannot be frozen (via p1141) in jog mode
(r0046.31 = 1).