Commissioning steps:
S Connect the line contactor control contact to DI/DO 8.
Note
Note the current carrying capacity of the digital output (see the Equipment
Manual). A line contactor may have to be used.
S Parameterize DI/DO 8 as an output (p728.8 = 1).
S Assign p0738 the control signal for the line contactor r0863.1.
S Connect the line contactor feedback contact to DI/DO 9.
S Assign p0860 an inverted input signal r0723.9.
S Enter the monitoring time for the line contactor (100 ms) in p0861.
Function diagram overview (refer to the List Manual)
S 8934
Parameter overview (see List Manual)
S r0863.1
S p0860
© Siemens AG 2006 All Rights Reserved
SINAMICS S120 Function Manual, 03/2006 Edition
Missing enable signals, line contactor control
CO/BO: Drive coupling status word/control word
BI: Line contactor, feedback signal
Infeed
Line contactor control
1-39