Function diagram overview (refer to the List Manual)
S 2701
4.3.3

Description

The "Simple brake control" function is used exclusively for controlling holding
brakes. The holding brake is used to secure drives against unwanted motion when
deactivated.
The trigger command for releasing and applying the holding brake is transmitted
via DRIVE-CLiQ from the Control Unit, which monitors and logically connects the
signals to the system-internal processes, directly to the Motor Module.
The Motor Module then performs the action and activates the output for the holding
brake. The sequence control, is shown in detail in the List Manual (FD 2701). The
operating principle of the holding brake can be configured via parameter p1215.
Fig. 4-4
© Siemens AG 2006 All Rights Reserved
SINAMICS S120 Function Manual, 03/2006 Edition
Simple brake control (r0108.14 = 0)
On command
1
Pulse enable
1
Magnetizing completed
Speed Setpoint
[
]
RPM
[
]
RPM
Actual speed
Output signal
1
Holding brake
Opening time
Function chart: simple brake control
p1226
n
threshold
p
1227
p1226
n
threshold
p
≥ 1
1228
Closing time
Extended Functions
Simple brake control
t
t
t
t
t
4-187