Operating Modes
Servo control
Signal chart
M_act
n_setp
p1542
Torque
reduction
p1545
Travel to
fixed stop
r1407.7
Torque
limit reached
r2199.11
Torque
utilization < p2194
Fig. 3-25
Signal chart for "Travel to fixed stop"
Commissioning
1. Activate travel to fixed end stop
Set p1545 = "1"
2. Set the desired torque limit
Example:
p1400.4 = "0" ––> upper or lower torque limit
p1520 = 100 Nm ––> effective in upper positive torque direction
p1521 = –1500 Nm ––> effective in lower negative torque direction
3. Run motor to fixed stop
The motor runs at the set torque until it reaches the stop and continues to work
against the stop until the torque limit has been reached, this status being
indicated in status bit r1407.7 "Torque limit reached".
3-118
Also for PROFIBUS
telegrams 102 to 106
M_limit
Fixed stop reached
© Siemens AG 2006 All Rights Reserved