Siemens SINAMICS S120 Function Manual page 20

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Infeed
Active Infeed
Operating modes of Active Infeed closed-loop control for Active Line Modules Chassis
Active Line Modules Chassis only function in Active Mode.
The DC link voltage setpoint (p3510) is preset in line with the supply voltage
(p0210) according to the following formula: p3510 = 1.5 * p0210.
Commissioning
During commissioning, the device supply voltage (p0210) and the rated line fre-
quency (p0211) must be parameterized. In addition, an optional line filter (p0220)
must be selected.
Note
In a supply system without regenerative feedback capability (e.g. generators),
regenerative operation must be inhibited via the binector input p3533.
The DC link voltage (p3510) can be set within the following limits:
S Booksize
– Upper limit: Maximum DC link voltage (p0280)
– Lower limit: Supply voltage (p0210) multiplied by 1.42
S Chassis
– Upper limit: Maximum DC link voltage (p0280)
– Lower limit: Supply voltage (p0210) multiplied by 1.42
Note
If automatic commissioning was carried out with STARTER, the line filter (if used)
must be included in the configuration.
Function diagram for Active Infeed (see List Manual)
S 1774
S 8920
S ...
S 8964
1-20
Overviews – Active Infeed
Control word sequential control infeed
Messages and monitoring, supply frequency and
Vdc monitoring
© Siemens AG 2006 All Rights Reserved
SINAMICS S120 Function Manual, 03/2006 Edition

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents