Activation
The bypass function with synchronization with overlap (p1260 = 1) can only be
activated using a control signal (p1267.0 = 1, p1267.1 = 0, p1267.2 = 0); it is not
possible to activate this function using a speed threshold or a fault.
Example
The following parameters must be set after the bypass function with synchroniza-
tion with overlap (p1260 = 1) has been activated.
Table 4-9
Parameter
p1266 =
p1267.0 = 1
p1267.1 = 0
p1267.2 = 0
p1269[0] =
p1269[1] =
p3800 = 1
p3802 = r1261.2
© Siemens AG 2006 All Rights Reserved
SINAMICS S120 Function Manual, 03/2006 Edition
Parameter setting for the bypass function with synchronization with overlap
Setting of the control signal for p1267.0 = 1
Bypass function is initiated by the control signal
Signal source to provide the feedback signal of contactor K1
Signal source to provide the feedback signal of contactor K2
The internal voltages are used for synchronization
Synchronization is activated by the bypass function
Extended Functions
Bypass (vector)
Description