Function Module "Cooling System" - Siemens SINAMICS S120 Function Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

4.22

Function module "cooling system"

Features
S Control and monitoring functions of a cooling system
S Automatically activated when using water-cooled power units
S Evaluation of a leakage water sensor (p0266.4)
S Evaluation of a water flow sensor (p0266.5, p0260, p0263)
S Evaluation of a conductivity sensor sensor (p0266.6, p0266.7, p0261, p0262)
S Monitoring the water intake temperature using internal temperature sensors
S Monitoring the flow rating using internal temperature sensors
Description
A cooling system (RKA) is responsible for cooling the water and the (non) conduc-
tivity in the de-ionized water cooling circuit of a water-cooled power unit. The cool-
ing system is controlled and monitored from a PLC that is part of the cooling sys-
tem. The cooling system function module described here is used as an interface
between the closed-loop control and the external control (open-loop) (PLC) of the
cooling system. The cooling system is controlled via terminals (e.g. Control Unit,
TM31).
© Siemens AG 2006 All Rights Reserved
SINAMICS S120 Function Manual, 03/2006 Edition
Extended Functions
Function module "cooling system"
4-233