Runtime (Operating Hours Counter) - Siemens SINAMICS S120 Function Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

4.5

Runtime (operating hours counter)

Total system runtime
The total system runtime is displayed in p2114 (Control Unit). Index 0 indicates the
system runtime in milliseconds after reaching 86.400.000 ms (24 hours), the value
is reset. Index 1 indicates the system runtime in days.
When the system is switched off, the counter value is saved.
When the drive unit is switched on, the counter continues to run with the value that
was saved when the system was last switched off.
Relative system runtime
The relative system runtime after the last POWER ON is displayed in p0969
(Control Unit). The value is in milliseconds and the counter overflows after 49 days.
Actual motor operating hours
The motor operating hours counter p0650 (drive) is started when the pulses are
enabled. When the pulse enable is withdrawn, the counter is stopped and the value
saved.
The value can only be stored with a CU320 with Order No. 6SL3040-....-0AA1 and
version C or higher.
If p0651 = 0, the counter is deactivated.
If the maintenance interval set in p0651 is reached, fault F01590 is triggered. Once
the motor has been maintained, the maintenance interval must be reset.
Operating hours counter for the fan
The operating hours of the fan in the power section are displayed in p0251.
The number of hours operated can only be reset to 0 in this parameter (e.g. after
the fan has been replaced). The service life of the fan is entered in p0252 (drive).
Alarm A30042 is output 500 hours before this figure is reached. Monitoring is deac-
tivated when p0252 = 0.
© Siemens AG 2006 All Rights Reserved
SINAMICS S120 Function Manual, 03/2006 Edition
Extended Functions
Runtime (operating hours counter)
4-195