Fixed Speed Setpoints - Siemens SINAMICS S120 Function Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Extended Setpoint Channel
Extended setpoint channel
2.2.3

Fixed speed setpoints

Description
This function can be used to specify preset speed setpoints. The fixed setpoints
are defined in parameters and selected via binector inputs. Both the individual fixed
setpoints and the effective fixed setpoint are available for further interconnection
via a connector output (e.g. to connector input p1070 – CI: main setpoint).
Properties
S Number of fixed setpoints:
S Selection of fixed setpoints:
– Binector input bits 0, 1, 2 and 3 = 0 –> setpoint = 0 active
– Unused binector inputs have the same effect as a "0" signal
Function diagram overview (refer to the List Manual)
S 1550
S 2503
S 3010
Parameter overview (see List Manual)
Adjustable parameters
S p1001[D]
S ...
S p1015[D]
S p1020[C]
S p1021[C]
S p1022[C]
S p1023[C]
Visualization parameters
S r1024
S r1197
Parameterization with STARTER
In the STARTER commissioning tool, the "Fixed setpoints" parameter screen in the
project navigator under the relevant drive is activated by double-clicking Setpoint
channel –> Fixed setpoints.
2-50
Fixed setpoint 1 to 15
Binector input bits 0 to 3
Overviews – setpoint channel
Status word sequence control
Fixed speed setpoints
CO: Fixed speed setpoint 1
CO: Fixed speed setpoint 15
BI: Fixed speed setpoint selection Bit 0
BI: Fixed speed setpoint selection Bit 1
BI: Fixed speed setpoint selection Bit 2
BI: Fixed speed setpoint selection Bit 3
CO: Fixed speed setpoint effective
Fixed speed setpoint current number
© Siemens AG 2006 All Rights Reserved