Commissioning And Operation; Function Check And Calibration - Siemens Acvatix SAX61 MO Series Basic Documentation

Table of Contents

Advertisement

Mechanically
Notes
Electrically
SA..61..
General notes on
calibration
Siemens
Smart Infrastructure
3.2

Commissioning and operation

3.2.1

Function check and Calibration

Before making the function check, the following preconditions must be satisfied:
· Environmental conditions specified in chapter "Technical data" (page 73)
· Actuator is mechanically connected to a Siemens valve
· Actuator is in "Manual operation" mode (page 69).
The actuator can be operated with the help of the "Manual adjuster" (see page 69).
Stroke
Manual adjuster
actuator
Actuator's
Turning in clockwise
stem
direction
extends
Turning in counter-
Actuator's
clockwise direction
stem retracts
· Ensure that the actuator's and valve's stem, or actuator's and valve's spindle are
securely connected in all positions.
· If the actuator is forced to travel beyond its end positions, overload protection
responds.
· Observe information given in chapter "Acting direction and flow characteristic"
on page 57.
Before making the function check, the following preconditions must be satisfied:
· Environmental conditions specified in chapter "Technical data" (page 73).
· Actuator is mechanically connected to a Siemens valve.
· Actuator is in "Automatic" mode (page 69).
Actuator and, if required, accessories are correctly fitted and connected. Also refer
to "Connection Terminals" (page 77)
· Power is applied.
Calibration is required with modulating actuators and SA..61.. before the function
check.
Before making the calibration, the following preconditions must be satisfied:
· A description of the calibration function is given in chapter "Calibration" (page 59
for non-Modbus actuators, page 63 for Modbus actuators).
· Housing cover is removed (step 6 "Special notes on mounting", page 35).
1
Bridge contact
If required, calibration can be repeated any number of times.
Actuators SAX.., SAY.., SAV.., SAL.. for valves
Handling
Rotary actuator
Actuator's spindle turns in
clockwise direction
Actuator's spindle turns in
counterclockwise direction
2
Check LED (page 70)
Control path
Bypass valve
valve AàAB
B à AB
Opening
Closing
Closing
Opening
43 / 87