Siemens SINAMICS S120 Function Manual page 310

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Basic Information about the Drive System
Data sets
Example: Switching between command data set 0 and 1
CDS
p0810 (0)
CDS effective
Fig. 5-3
DDS: Drive Data Set
A drive data set contains various adjustable parameters that are relevant with
respect to open and closed-loop drive control:
S Numbers of the assigned motor and encoder data sets:
– p0186: assigned motor data set (MDS)
– p0187 to p0189: up to 3 assigned encoder data sets (EDS)
S Various control parameters, e.g.:
– Fixed speed setpoints (p1001 to p1015)
– Speed limits min./max. (p1080, p1082)
– Characteristic data of ramp-function generator (p1120 ff)
– Characteristic data of controller (p1240 ff)
– ...
The parameters that are grouped together in the drive data set are identified in the
SINAMICS parameter list by "Data Set DDS" and are assigned an index [0..n].
More than one drive data set can be parameterized. You can switch easily between
different drive configurations (control type, motor, encoder) by selecting the
corresponding drive data set.
5-310
0
1
r0836 = 0
0
1
1
r0050 = 0
Switching the command data set (example)
CDS selected
r0836 = 1
2
t
Changeover time
r0050 = 1
t
© Siemens AG 2006 All Rights Reserved
SINAMICS S120 Function Manual, 03/2006 Edition
cds_1.vsd