Siemens SINAMICS S120 Function Manual page 326

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Basic Information about the Drive System
BICO technology: interconnecting signals
Scaling for object A_Inf
Table 5-8
Scaling for object A_Inf
Quantity
Reference frequency
Reference voltage
Reference current
Reference power
Reference control factor
Reference temperature
Reference electrical angle
Scaling for object B_Inf
Table 5-9
Scaling for object B_Inf
Quantity
Reference frequency
Reference voltage
Reference current
Reference power
Reference temperature
Reference electrical angle
5-326
Scaling parameter
100 % = p2000
100 % = p2001
100 % = p2002
100 % = r2004
100 % = Maximum output voltage
without overload
100 % = 100°C
100 % = 90°
Scaling parameter
100 % = p2000
100 % = p2001
100 % = p2002
100 % = r2004
100 % = 100°C
100 % = 90°
Default at initial
commissioning
p2000 = p0211
p2001 = r0206/r0207
p2002 = p0207
r2004 = p0206
Default at initial
commissioning
p2000 = 50
p2001 = r0206/r0207
p2002 = p0207
r2004 = p0206