Table 8-15 1Count 24V/100Khz Error Types - Siemens Simatic ET 200S Operating Instructions Manual

Distributed i/o system
Hide thumbs Also See for Simatic ET 200S:
Table of Contents

Advertisement

1COUNT 24V/100kHz error types
The table below shows the error displays on the 1COUNT 24V/100kHz.
Table 8-15
1COUNT 24V/100kHz error types
Error class
1
00001: Short circuit
D
5
00101: Excess temperature
D
6
00110: Wire break
D
9
01001: Fault
D
16
10000: Parameter assignment
D
error
1COUNT 5V/500kHz error types
The table below shows the error displays on the 1COUNT 5V/500kHz.
Table 8-16
1COUNT 5V/500kHz error types
Error class
1
00001: Short circuit
D
5
00101: Excess temperature
D
6
00110: Wire break
D
9
01001: Fault
D
16
10000: Parameter assignment
D
error
26
11010: External error
D
1STEP 5V/204kHz error types
The table below shows the error displays on the 1STEP 5V/204kHz.
Table 8-17
1STEP 5V/204kHz error types
Error class
1
00001: Short circuit
D
9
01001: Fault
D
16
10000: Parameter assignment
D
error
ET 200S
Operating Instructions, 12/2005, A5E00515771-03
8.1 Alarm, error and system messages on PROFIBUS DP
Meaning
Short circuit of the sensor supply or the
actuator.
Digital output is overloaded.
Line to the actuator interrupted.
Internal module error occurred.
Load voltage from the power module is
too low.
Parameters have not been assigned to
the module.
Meaning
Short circuit of the sensor supply or the
actuator.
Digital output is overloaded.
Line to the actuator interrupted.
Internal module error occurred.
Parameters have not been assigned to
the module.
Wire break/short circuit of the 5 V
sensor signals:
A, /A, B, /B, N, /N,
Meaning
Short circuit of the sensor supply.
Internal module error occurred.
Parameters have not been assigned to
the module.
Alarm, error and system messages
Remedy
Check the wiring to the sensor. Correct
the process wiring.
Correct the process wiring.
Correct the process wiring.
Replace the module.
Correct the process wiring. Check the
load voltage.
Correct the parameter assignment.
Remedy
Check the wiring to the sensor. Correct
the process wiring.
Correct the process wiring.
Correct the process wiring.
Replace the module.
Correct the parameter assignment.
Correct the parameter assignment.
Remedy
Check the wiring to the switches.
Correct the process wiring.
Replace the module.
Correct the parameter assignment.