Siemens Simatic ET 200S Operating Instructions Manual page 236

Distributed i/o system
Hide thumbs Also See for Simatic ET 200S:
Table of Contents

Advertisement

Interface modules
10.5 Interface module IM151-1 STANDARD (6ES7151-1AA04-0AB0)
Technical data IM151-1 STANDARD (6ES7151-1AA04-0AB0)
Dimension W x H x D (mm)
Weight
Transmission rate
Bus protocol
Interfaces
SYNC capability
FREEZE capability
Manufacturer ID
Direct data exchange
Isochronous operation
Parameter length
Address space
Option handling
I&M data
Firmware update
Max. output current of the PROFIBUS DP
interface (5, 6)
Rated supply voltage of the electronic
components (1L+)
Isolation
Permitted potential difference (to the rail)
Insulation test voltage
Current consumption from rated supply
voltage (1L+)
Power dissipation of the module
Interrupts
Diagnostic function
10-14
Reverse polarity protection
Power failure bypass
Between the backplane bus and
electronic components
Between the PROFIBUS DP and
electronic components
Between the supply voltage and
electronic components
Group error
PROFIBUS DP bus monitoring
Monitoring of the power supply voltage of
the electronics
Dimensions and weight
45 x 119.5 x 75
Approx 150 g
Module-specific data
9.6; 19.2; 45.45; 93.75; 187.5; 500 kBaud, 1.5; 3; 6;
12 Mbit/s
PROFIBUS DP
RS 485
Yes
Yes
806A
H
Yes
No
27 bytes
244 bytes I/O
Yes
Yes
via PROFIBUS DP
80 mA
Voltages, currents, potentials
24 VDC
Yes
min. 20 ms
No
Yes
No
75 VDC, 60 VAC
500 VDC
Approx. 200 mA
Typically 3.3 W
Status, interrupts, diagnostics
Yes
Yes
red LED "SF"
Red "BF" LED
Green "ON" LED
Operating Instructions, 12/2005, A5E00515771-03
ET 200S

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents