Resolution (including overrange)
Cycle time (per module)
Settling time
•
•
•
Crosstalk between the outputs
Operational limit (in the entire temperature range,
with reference to the output range)
Basic error limit (operational limit at 25 °C with
reference to output range)
Temperature error (with reference to the output
range)
Linearity error (with reference to the output range) ± 0.01% (for resistive load)
Repeatability
(in steady state at 25 °C with reference to output
range)
Output range (rated value)
Load impedance (in the rated range of the output)
•
•
Current output
•
Destruction limit against voltages/currents applied
from outside
•
•
Connection of actuators
•
I&M Functions
Reading of the I&M data from the module is possible with interface modules as from a higher
MLFB or as from a higher version than described in the following table:
ET 200S
Product Information, 03/2006, A5E00743001-01
New Information About the "ET 200S Distributed I/O System Manual"
0
4.22 2AO I High Feature Analog Electronic Module (6ES7135-4MB02-0AB0)
For resistive load
For capacitive load
For inductive load
For current outputs
For inductive load
Open circuit voltage
Voltage at the outputs to M
Current
Current output two-wire connection
Analog value generation
± 20 mA / 15 bits + sign
4 mA to 20 mA / 15 bits
max. 0.5 ms
0.3 ms
1.0 ms
0.5 ms
Suppression of interference, limits of error
< - 60 dB
± 0.1 %
± 0.05 %
± 0.003%/K
± 0.01 %
Measuring Transducer Selection Data
± 20 mA
4 to 20 mA
max. 500 Ω
1 mH
18 V
15 V continuous; 75 V for max. 1 ms
ANA
(sampling ratio 1:20)
max. 50 mA DC
Yes
3-21