Resolution (including overrange)
Cycle time (per module)
Settling time
Crosstalk between the outputs
Operational limit (in the entire temperature range,
with reference to the output range)
Basic error limit (operational limit at 25 °C with
reference to output range)
Temperature error (with reference to the output
range)
Linearity error (with reference to the output range) ± 0.01% (for resistive load)
Repeatability
(in steady state at 25 °C with reference to output
range)
Output range (rated value)
Load impedance (in the rated range of the output)
Current output
Destruction limit against voltages/currents applied
from outside
Connection of actuators
I&M Functions
Reading of the I&M data from the module is possible with interface modules as from a higher
MLFB or as from a higher version than described in the following table:
ET 200S
Product Information, 03/2006, A5E00743001-01
New Information About the "ET 200S Distributed I/O System Manual"
0
4.22 2AO I High Feature Analog Electronic Module (6ES7135-4MB02-0AB0)
For resistive load
For capacitive load
For inductive load
For current outputs
For inductive load
Open circuit voltage
Voltage at the outputs to M
Current
Current output two-wire connection
Analog value generation
± 20 mA / 15 bits + sign
4 mA to 20 mA / 15 bits
max. 0.5 ms
0.3 ms
1.0 ms
0.5 ms
Suppression of interference, limits of error
< - 60 dB
± 0.1 %
± 0.05 %
± 0.003%/K
± 0.01 %
Measuring Transducer Selection Data
± 20 mA
4 to 20 mA
max. 500 Ω
1 mH
18 V
15 V continuous; 75 V for max. 1 ms
ANA
(sampling ratio 1:20)
max. 50 mA DC
Yes