Option handling in PIQ/PII
Figure 7-7
(*)
PIQ: AB x to AB x+7
Slot 2 to 63:
PII: EB x to EB x+7
Slot 1 to 63:
ET 200S
Operating Instructions, 12/2005, A5E00515771-03
Option handling in PIQ/PII
not relevant
0
Parameter assignment for option handling applies. RESERVE
modules are allowed:
The station is engaged in data exchange.
•
A diagnostic is not signaled.
•
The SF LED on the interface module is off.
•
1
Parameter assignment for option handling is cancelled.
RESERVE modules are not accepted on this slot:
The station is engaged in data exchange.
•
A diagnostic is not signaled.
•
The SF LED on the interface module is off.
•
0
The RESERVE module, an incorrect module, or a removed
module is on the slot.
1
The configured module is on the slot.
7.3 Option handling on PROFIBUS DP
Functions
7-15