Commissioning
6.3 Commissioning on PROFINET IO
GSD file
You configure the ET 200S using the GSD file. This file is used to integrate the ET 200S in
your system as an IO device. You can download the GSD file for ET 200S at the following
address:
http://support.automation.siemens.com/WW/view/de/19699080
The following GSD file is available for the IM151-3 interface module:
GSDML-V1.0-Siemens-ET200S-"Date in yyyymmdd".xml
You can find further information about the procedure in the
6.3.2

Assigning device names to the I/O device

Introduction
Each PROFINET IO device is assigned a unique device ID by the manufacturer (MAC
address).
For configuration and in the user program, each ET 200S IO device is addressed with its
device name.
For detailed information on addressing in PROFINET IO, refer to the
Description
Requirements
• IM151-3 Interface Module
• SIMATIC Micro Memory Card 64k and higher
• The PD must be online on PROFINET to the IO device to let you assign a device name to
• The IO device is configured in HW Config and assigned an IP address.
Assigning a device name
1. Insert an empty SIMATIC Micro Memory Card into the module slot in the front of the
2. Switch on the power supply for the IM151-3 PN.
3. Open the Properties - IM151-3 PN or Properties - IM151-3 PN HIGH FEATURE window
Transfer the device name to the interface module.
1. In HW Config select PLC > Ethernet > Assign Device Name.
2. Click the Assign name button in the Assign device name window.
6-14
.
the interface module.
IM151-3.
in the HW Config and enter the device name for the IO device there and confirm with OK.
You can use any device name except for "noname" (not case-sensitive).
STEP 7
Online Help.
PROFINET System
Operating Instructions, 12/2005, A5E00515771-03
ET 200S