Commissioning
6.2 Commissioning on PROFIBUS DP
Configuration table and address space
The user is free to select the byte addresses of the inputs and outputs (if the configuration
software supports this). The bit addresses result automatically from the sequence of the
grouped modules.
The following table shows which modules have been grouped and the corresponding
address space.
Table 6-1
Configuration table and address space
Slot
Module
1
6ES7 138-4CA01-0AA0 PM-E 24 VDC
2
6ES7131-4BB01-0AB0 2DI 24 VDC
3
6ES7131-4BB01-0AB0* 2DI 24 VDC
4
6ES7134-4FB01-0AB0 2AI U
5
6ES7135-4GB01-0AB0 2AO I
6
6ES7131-4BD01-0AA0* 4DI 24 VDC
7
6ES7132-4BD01-0AA0 4DO 24 VDC
8
6ES7132-4BB01-0AB0* 2DO 24 VDC
9
6ES7132-4HB01-0AB0* 2DO Rel.
10
6ES7134-4FB01-0AB0 2AI U
11
6ES7135-4GB01-0AB0 2AO I
12
6ES7138-4CA01-0AA0 PM-E 24 VDC
13
6ES7132-4BB31-0AB0 2DO 24 VDC
14
6ES7132-4BB31-0AB0* 2DO 24 VDC
15
6ES7138-4CB11-0AB0 PM-E AC230
16
6ES7132-4FB01-0AB0* 2DO 230V
17
6ES7132-4FB01-0AB0* 2DO 230V
18
3RK1903-0BA00 PM-D
19
3RK1301-xxB00-0AA0 DS
20
3RK1301-xxB00-0AA0 *DS
21
3RK1301-xxB00-0AA0 DS
6-8
Grouping
I/O address
Inputs
---
---
Yes
0.0 to 0.1
0.2 to 0.3
No
1 to 4
No
Yes
0.4 to 0.7
Yes
No
5 to 8
No
---
---
Yes
Yes
---
---
Yes
Yes
---
---
Yes
9.0 to 9.3
9.4 to 9.7
Yes
10.0 to 10.3
Operating Instructions, 12/2005, A5E00515771-03
Outputs
---
0 to 3
4.0 to 4.3
4.4 to 4.5
4.6 to 4.7
5 to 8
---
9.0 to 9.1
9.2 to 9.3
---
9.4 to 9.5
9.6 to 9.7
---
10.0 to 10.3
10.4 to 10.7
11.0 to 11.3