Commissioning And Startup Of Et 200S On Profibus Dp - Siemens Simatic ET 200S Operating Instructions Manual

Distributed i/o system
Hide thumbs Also See for Simatic ET 200S:
Table of Contents

Advertisement

6.2.2

Commissioning and startup of ET 200S on PROFIBUS DP

6.2.2.1
Setting the PROFIBUS Address
Introduction
The PROFIBUS address is used to specify the address of the ET 200S distributed I/O
system on PROFIBUS DP.
• The PROFIBUS DP address for the ET 200S is set on the interface module or COMPACT
• Valid PROFIBUS DP addresses are 1 to 125.
• Each address can be assigned only once on PROFIBUS DP.
Requirements
Address setting is not yet assigned on PROFIBUS DP.
Required tools
3-mm screwdriver
Setting the PROFIBUS DP address
1. Slide the window
2. Use a screwdriver to set the desired PROFIBUS DP address via the DIP switch.
3. Close the window.
ET 200S
Operating Instructions, 12/2005, A5E00515771-03
module by means of DIP switches. The DIP switches are to be found on the front of the
interface module, protected by a sliding window.
– upwards on the interface module.
– downwards on the COMPACT module.
Caution
When open, the window protrudes out from underneath the COMPACT module case.
This can cause it to be easily broken off.
6.2 Commissioning on PROFIBUS DP
Commissioning
6-9