Siemens Simatic ET 200S Operating Instructions Manual page 410

Distributed i/o system
Hide thumbs Also See for Simatic ET 200S:
Table of Contents

Advertisement

New Information About the "ET 200S Distributed I/O System Manual"
0
4.20 2AO U High Feature Analog Electronic Module (6ES7135-4LB02-0AB0)
3-16
Cycle time per module
Resolution (including overrange)
Settling time
For resistive load
For capacitive load
For inductive load
Crosstalk between the outputs
Operational limit
(in the entire temperature range, with reference to
the output range)
Basic error limit (operational limit at 25 °C with
reference to output range)
Temperature error (with reference to the output
range)
Linearity error (with reference to the output range) ± 0.01 %
Repeatability (in steady state at 25 °C with
reference to output range)
Output range (rated value)
Load impedance (in the rated range of the output)
At voltage outputs capacitive load
Voltage output
Short-circuit protection
Short-circuit voltage
Destruction limit against voltages/currents applied
from outside
Voltage at the outputs to M
Connection of actuators
Voltage output
2-wire connection
4-wire connection
Analog Value Generation
0.5 ms
± 5 V / 15 bits + sign
± 10 V / 15 bits + sign
1 V to 5 V / 15 bits
0.3 ms
0.5 ms
0.5 ms
Interference Suppression, Error Limits
Min. -60 dB
± 0.1 %
± 0.05 %
± 0.003%/K
± 0.01 %
Actuator Selection Data
± 5 V
± 10 V
1 V to 5 V
Min. 1.0 kΩ
Max. 0.5 µF
Yes
Approx. 25 mA
Max. 15 V continuous; 75 V for max. 1 ms
ANA
(sampling ratio 1:20)
Possible, without compensation of the line
resistances
Possible
Product Information, 03/2006, A5E00743001-01