Siemens Simatic ET 200S Operating Instructions Manual page 98

Distributed i/o system
Hide thumbs Also See for Simatic ET 200S:
Table of Contents

Advertisement

Wiring and assembly
5.4 Wiring the ET 200S
Example configuration of a fiber-optic cable network with IM151-1 FO STANDARD
The figure below presents an example of how to set up a fiber-optic cable network with the
ET 200S and the IM151-1 FO STANDARD interface module.
3
Figure 5-9
Installing simplex connectors
Note
The fiber-optic duplex cable may have the following maximum lengths:
• PROFIBUS Plastic Fiber Optic standard cable
• PROFIBUS PCF Fiber Optic standard cable
1. Remove approximately 30 cm of the jacket of the fiber-optic duplex cable.
2. Attach the fiber-optic duplex cable with the associated simplex plugs. You can find
5-18
1
Fiber-optic cable network with IM151-1 FO STANDARD
S7-400H automation system with IM 467 FO as the DP master
ET 200S Distributed I/O with IM151-1 FO STANDARD
Fiber-optic duplex cable
detailed installation instructions in the
Hint: Do not click the 2 simplex plugs closed individually, click them closed together so
that they a complete a "duplex plug". In this manner you will achieve a better hold in the
plug adapter.
IMPORTANT: The smoothed and polished surface of the plastic fibers must be absolutely
flat and even. Likewise, the plastic jacket must not protrude or be cut unevenly. Every
irregularity causes strong attenuation of the light signal via the fiber-optic cable!
2
50 m
300 m
SIMATIC NET- PROFIBUS Networks
Operating Instructions, 12/2005, A5E00515771-03
manual.
ET 200S

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents