Error Types - Siemens SIMATIC ET 200S Operating Instructions Manual

Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

1Count24V
2.11 Diagnostics
2.11.2

Error types

For information on the structure of the channel-related diagnostics, refer to the manual on
the interface module used in your ET 200S station.
1Count24V error types
The following table shows the error types on the 1Count24V.
Error type
1
00001: Short circuit
D
5
00101: Overtemperature
D
6
00110: Cable break
D
9
01001: Error
D
16
10000: Parameter assignment
D
error
112
Meaning
Short circuit of the sensor supply or the
actuator.
The digital output is overloaded.
Line to the actuator is interrupted.
Internal module error occurred.
Load voltage from the power module is
too low.
Parameters have not been assigned to
the module.
Remedy
Check the wiring to the sensor. Correct
the process wiring.
Correct the process wiring.
Correct the process wiring.
Replace the module.
Correct the process wiring. Check the
load voltage.
Correct the parameter assignment.
Technological Functions
Operating Instructions, 06/2010, A5E00124867-07