Commissioning
6.2 Commissioning on PROFIBUS DP
DPV1 operation
If you are using IM151-1 STANDARD (6ES7151-1AA04-0AB0 or higher) in DPV1 mode on
an S7 CPU that does not support an insert/remove module interrupt, you must not enable
the "Operation at preset <> actual configuration" parameter in
removal of a module (module failure) always results in a station failure (OB 86).
If it is imperative that you enable "Operation at preset <> actual configuration", you must
either select DPV0 mode or configure IM151-1/FO STANDARD using the GSD file (under
"Additional field devices - I/O" in the
actual configuration" is then possible even when the insert/remove module interrupt is
disabled.
However, the S7-CPU does not register an insertion or removal (module failure). You can
detect such events only by cyclically reading the diagnostic frame and evaluating the module
status.
Configuring by means of the GSD file
You configure the ET 200S distributed I/O system using the GSD file. The ET 200S is linked
as norm slave in your system via the GSD file. You can download the GSD file for ET 200S
on the Internet at the following address:
http://support.automation.siemens.com/WW/view/de/652154
The following GSD files are available:
• IM151-1 BASIC: "SIEM80F3.GSx"
• IM151-1 STANDARD:
• IM151-1 FO STANDARD "SI03806B.GSx"
• IM151-1 HIGH FEATURE
• IM151-1 COMPACT 32DI: "SIEM8201.GSx"
• IM151-1 COMPACT 16DI/16DO: "SIEM8200.GSx"
6-2
Note
The ET 200S is included in the hardware catalog of HW Config:
STEP 7
• IM151-1 BASIC:
• IM151-1 COMPACT: f
"ET 200S/COMPACT"
• IM151-1 STANDARD:
• IM151-1 FO STANDARD
• IM151-1 HIGH FEATURE from
You will not need a GSD file. Advantages:
• Simplified summary of the devices (via the "Pack addresses" button in HW Config)
• Validity checking of parameters
You can find further information about the procedure in the
– to 6ES7151-1AA02-0AB0: "SIEM806A.GSx"
– to 6ES7151-1AA03-0AB0: "SI03806A.GSx"
– to 6ES7151-1BA00-0AB0: "SI0180E0.GSx"
– to 6ES7151-1BA01-0AB0: "SI0280E0.GSx"
V5.2 and higher
STEP 7
V5.3 and higher with Service Pack 3 + HSP
STEP 7
V5.0 and higher with Service Pack 3
STEP 7
V5.1 and higher with Service Pack 1
STEP 7
V5.1 and higher with Service Pack 3
STEP 7
hardware catalog). "Operation at preset <>
STEP 7
Online Help.
STEP 7
. Otherwise, the
Operating Instructions, 12/2005, A5E00515771-03