Example for the calculation of the ET 200S response time for the IM151-1 HIGH FEATURE
(6ES7151-1BA01-0AB0)
Example set-up for the calculation of the response time for the IM151-1 HIGH FEATURE
(6ES7151-1BA01-0AB0)
Calculation method:
m = 17; b = 0
Response time [µs] = 22 · m + 14 · b + 213
Response time [µs] = 22 · 17 + 14 · 0 + 213
Response time [µs] = 587 µs
D.4
Response time for digital input modules
D.4
Input delay
The reaction times of the digital input modules depend on the input delay.
Reference
Information on the input delays of the respective digital electronic modules are to be found in
the
D.5
Response time for digital output modules
D.5
Output delay
The response times correspond to the output delay.
Reference
Information on the output delays of the respective digital electronic modules are to be found
in the
ET 200S
Operating Instructions, 12/2005, A5E00515771-03
ET 200S device manual
ET 200S device manual
D.4 Response time for digital input modules
in the Technical Data of the relevant modules.
in the Technical Data of the relevant modules.
Response times
D-5