Technical data IM151-1 COMPACT 32DI 24 VDC (6ES7151-1CA00-1BL0)
Dimension W x H x D (mm)
Weight
Transmission rate
Bus protocol
Interfaces
SYNC capability
FREEZE capability
Manufacturer ID
Direct data exchange
Isochronous operation
Parameter length
Address space
Option handling
I&M data
Firmware update
Max. output current of the PROFIBUS DP
interface (5, 6)
Power dissipation of the module
Rated supply voltage of the electronic
components (1L+)
Isolation
Permitted potential difference (to the rail)
Insulation test voltage
Current consumption from rated supply voltage
(1L+)
Interrupts
Diagnostic functions (for PROFIBUS DP)
Diagnostic functions (for internal periphery)
ET 200S
Operating Instructions, 12/2005, A5E00515771-03
Reverse polarity protection
Power failure bypass
Between the backplane bus and electronic
components
Between the PROFIBUS DP and electronic
components
Between the supply voltage and electronic
components
Group error
PROFIBUS DP bus monitoring
Monitoring of the power supply voltage of the
electronics
11.4 IM151-1 COMPACT 32DI 24 VDC (6ES7151-1CA00-1BL0)
Dimensions and weight
120 x 81 x 58
Approx 230 g
Module-specific data
9.6; 19.2; 45.45; 93.75; 187.5; 500 kBaud,
1.5; 3; 6; 12 Mbit/s
PROFIBUS DP
RS 485
Yes
Yes
8201
Yes
No
23 bytes
100-byte inputs / 100-byte outputs
No
No
No
80 mA
Typically 3 W
Voltages, currents, potentials
24 VDC
Yes
No
No
Yes
No
75 VDC, 60 VAC
500 VDC
Approx. 100 mA
Status, interrupts, diagnostics
None
Yes
module granular
(A peripheral fault will not cause the station to fail.)
Red "SF" LED
red "BF" LED
Green "ON" LED
COMPACT modules