Siemens Simatic ET 200S Operating Instructions Manual page 45

Distributed i/o system
Hide thumbs Also See for Simatic ET 200S:
Table of Contents

Advertisement

Simulating a wire break in the actuator wiring
1. Remove the cable from terminal 1 on the 2DO 24 VDC/0.5 A; HF electronic module
2. Observe the status LEDs:
3. Evaluate diagnostic data record C00A
Header information
0 and 1
2 and 3
4 and 5
Channel diagnostic data
6 and 7
8 and 9
10 and 11
14 and 15
Channel diagnostic data record 0 with detailed information on the fault
16 and 17
20 and 21
1. Reattach the cable to the actuator in terminal 1, and reevaluate the diagnostics:
ET 200S
Operating Instructions, 12/2005, A5E00515771-03
(slot 7)
IM151-3 PN:
– SF: lights up
Electronic module 2DO 24 VDC/0.5 A High Feature:
– SF: lights up → a diagnostic message is pending.
– 1: off → output is not activated
Byte
Table of
Contents
0010
H
0012
H
0100
H
0007
H
0001
H
8000
H
12
08
H
13
00
H
8000
H
0000
H
18
48
H
19
01
H
0006
H
– Status LEDs on the IM151-3 PN interface module:
SF: off
– Status LEDs electronic module 2DO 24 VDC/0.5 A HF:
SF: off
1: off/on
– The diagnostic message is deleted.
Brief instructions on commissioning ET 200S
.
H
Data record with channel diagnostics
18 bytes follow
Version 1.0
Slot 7
Submodule slot 1
Error on submodule
incoming error
Reserved
Submodule diagnostic is pending
Channel 0
Incoming error on an output
Data type: 1 bit
Wire break
2.2 Commissioning on PROFINET IO
Meaning
2-21