3. In the event of a remove interrupt, OB 83 is started. Start SFB 52 in OB 1. Evaluate the
Header information
0 and 1
2 and 3
4 and 5
6 and 7
IO device header information
8 and 9
10 and 11
12 and 13
Configuration data of slots
14 and 15
16 to 19
20 and 21
22 and 23
1. Reinsert the removed electronic module into the terminal module.
Switching off load voltage on the power module
1. Switch off the load voltage on the PM-E 24 VDC (slot 1).
2. Observe the status LEDs.
ET 200S
Operating Instructions, 12/2005, A5E00515771-03
E002 diagnostic data record
Byte
Table of
Contents
8104
H
0014
H
0100
H
0001
H
0000
H
0000
H
0001
H
0002
H
XXXXXXXX
H
0000
H
0000
H
Result:
– Status LEDs on the IM151-3 PN interface module:
SF: off
BF: off
ON: lights up
– Once the module is inserted, diagnostic data record E002
discrepancy between the preset and actual configurations for any slot.
IM151-3 PN:
– SF: lights up
Power module:
– PWR: off → No load voltage available on the power module
Brief instructions on commissioning ET 200S
.
H
Data record with discrepancies between the preset and actual
configurations
20 bytes follow
Version 1.0
0001
if the preset configuration deviates from the actual
H
configuration
steady
steady
Number of slots in which there is a discrepancy between the preset
configuration and the actual configuration
Slot number of the slot with a discrepancy between the preset and
actual configurations
Identification of the inserted module
No module inserted
Number of submodule slots with a discrepancy between the preset
and actual configurations. Because the content is 0000
additional submodule data follow.
2.2 Commissioning on PROFINET IO
Meaning
no longer indicates a
H
, no
H
2-19