Assigning device names for the IO device

Procedure
1. Insert the SIMATIC Micro Memory Card in the IM151-3 PN.
2. Switch on the power supply for the IM151-3 PN interface module.
3. Open the "Properties - IM151-3 PN" window in the HW Config and enter the device name
4. An online PROFINET connection from the programming device to the IO device via a
2.2.5
Creating a user program
Procedure
1. Create the user program in the LAD/STL/FBD editor in OB 1.
STL
A E 0.0
A M 2.0
S A 0.0
Example 2: Transferring an input byte to an output byte:
STL
L PEB 0
T PAB 0
1. Save the project in SIMATIC Manager.
2. Download the configuration to the IO controller.
ET 200S
Operating Instructions, 12/2005, A5E00515771-03
for the IO device there.
switch is required for in order to transfer the name to the IM151-3 PN interface module.
The device name is transferred to the IM151-3 PN using "PLC > Ethernet > Assign
Device Name." To do so, activate the "Assign name" button in the "Assign device name"
window. The device name is stored on the SIMATIC Micro Memory Card in the interface
module IM151-3 PN.
Once the name is assigned, it appears in the window.
Example 1: Reading an input and controlling an output:
Brief instructions on commissioning ET 200S
2.2 Commissioning on PROFINET IO
If input byte 0.0 and
memory bit 2.0 is set, then
set output byte 0.0
Load I/O input byte 0 in the accumulator
(bytes 0.0 to 0.7)
Transfer the accumulator content to
I/O output byte 0 (bytes 0.0 to 0.7)
2-15