Diagnostics

3.2 Error types

3.2
Error types
Analog input module error types
Table 3-1
16
D
9
D
7
D
8
D
6
D
21
D
Reference channel error is not reported if the RTD module is not parameterized in the GSD file using
the PT100 Climatic. This applies to IM151-1 HIGH FEATURE (6ES7151-1BA00-0AB0 or higher),
IM151-7 CPU and IM151-3 PROFINET IO (6ES7151-3AA00-0AB0 or higher).
16
Error types
Error type
10000:
Module cannot use the
Parameter
parameter for the channel:
assignment
Inserted module does not
error
match the one configured.
Incorrect parameter
assignment.
01001: Error
Internal module error
(diagnostic message at
channel 0 applies to the entire
module)
00111: Upper
Value is above the overrange.
limit exceeded
01000: Lower
Value is below the underrange. Correct the module/final
limit value
undershot
00110:
Line to the encoder
Open circuit
interrupted.
10101:
Error on the reference channel
Reference
channel error
*
Meaning
Correct the configuration (align
actual and set configuration).
Correct the parameter
assignment (wire break
diagnostics only parameterized
for the permitted measuring
ranges).
Replace the module.
Correct the module/final
controlling element tuning.
controlling element tuning.
Correct the process wiring.
Check the reference module (2
AI RTD ST).
2AI TC ST analog electronic module (6ES7134-4JB00-0AB0)
Manual, 04/2007, A5E01076883-01
Remedy