Siemens Simatic ET 200S Operating Instructions Manual page 406

Distributed i/o system
Hide thumbs Also See for Simatic ET 200S:
Table of Contents

Advertisement

New Information About the "ET 200S Distributed I/O System Manual"
0
4.13 2AI I 2/4WIRE High Feature Analog Electronic Module (6ES7134-4MB02-0AB0)
Input range (rated value) / measurement
resistance
Permissible input current
Load of the two-wire transmitter:
Smoothing of the measured values
I&M Functions
Reading of the I&M data from the module is possible with interface modules as from a higher
MLFB or as from a higher version than described in the following table:
Interface module
IM151-1 STANDARD
IM151-1 FO STANDARD
IM151-1 HIGH FEATURE
IM151-3 PN
IM151-3 PN HIGH FEATURE
IM151-7 CPU-F
IM151-7 CPU
IM151-7 CPU FO
3-12
Current
Sensor Selection Data
Approx. 44 Ω
Approx. 50 mA (can be limited electronically)
max. 750 Ω
Yes, parameters can be assigned in 4 steps by
means of digital filtering
Step
None
Weak
Medium
Strong
Order no. [MLFB]
6ES7151-1AA04-0AB0
6ES7151-1AB02-0AB0
6ES7151-1BA01-0AB0
6ES7151-3AA20-0AB0
6ES7151-3BA20-0AB0
6ES7151-7FA01-0AB0
6ES7151-7AA11-0AB0
6ES7151-7AB00-0AB0
Product Information, 03/2006, A5E00743001-01
Time constant
1 x cycle time
4 x cycle time
16 x cycle time
32 x cycle time
Product version
04
04
02
01
01
03
01
03
ET 200S