Table 8-9 Power Module Error Types - Siemens Simatic ET 200S Operating Instructions Manual

Distributed i/o system
Hide thumbs Also See for Simatic ET 200S:
Table of Contents

Advertisement

Alarm, error and system messages
8.1 Alarm, error and system messages on PROFIBUS DP
Power module error types
The diagnostic message is reported on channel 0 and applies to the whole module.
The table below shows the error types on power modules
Table 8-9
Power module error types
Power module electronic
modules
PM-E
PM-E 24VDC
24 ..48 VDC/
PM E
120 ..230 VAC
24 ..48 VDC
---
COMPACT modules error types
The table below shows the error types on COMPACT modules.
Table 8-10
COMPACT modules error types
COMPACT modules
32DI
16DI/16DO
8-34
Error class
17
10001: Sensor or load
D
voltage missing
18
10010: Fuse defective
D
Error class
17
10001: Load voltage
D
missing
1
00001: Short circuit
D
17
10001: Load voltage
D
missing
1
00001: Short circuit
D
Meaning
Power supply voltage
not present or too low.
The fuse in the power
module has tripped.
Meaning
Load voltage not
available (due to wire
break or short circuit)
or too low. Diagnostic
message is issued for
the relevant voltage
group.
Short circuit of the
sensor supply.
Diagnostic message is
issued for the relevant
voltage group.
Load voltage not
available (due to wire
break or short circuit)
or too low. Diagnostic
message is issued for
the relevant voltage
group.
Short circuit of the
sensor supply.
Diagnostic message is
issued for the relevant
voltage group.
Operating Instructions, 12/2005, A5E00515771-03
Remedy
Correct the process
wiring. Check the supply
voltage.
Replace the fuse.
Remedy
Correct the process
wiring. Check the load
voltage.
Correct the process
wiring (sensor wiring).
Correct the process
wiring. Check the load
voltage.
Correct the process
wiring (sensor wiring).
ET 200S