9.4

Mechanical and Climatic Ambient Conditions

9.4
Climatic ambient conditions
The following climatic ambient conditions apply:
Ambient conditions
Temperature
Temperature change
Relative humidity
Air pressure
Contaminant concentration
* Restrictions for area of application: 0 to 55/50 °C, vertically mounted
This area of application of 0 to 55 °C (vertically-mounted) is permitted for the following
modules only:
• IM151-1 STANDARD: 6ES7151-1AA02-0AB0
• PM-E 24 VDC: 6ES7138-4CA01-0AA0
• 2DI 24 VDC ST: 6ES7131-4BB01-0AA0
• 2DI 24 VDC HF: 6ES7131-4BB01-0AB0
• 4DI 24 VDC ST: 6ES7131-4BD01-0AA0
• 4DI 24 VDC HF: 6ES7131-4BD01-0AB0
• 2DO 24 VDC/0.5 A ST: 6ES7132-4BB01-0AA0
• 2DO 24 VDC/0.5 A HF: 6ES7132-4BB01-0AB0
• 4DO 24 VDC/0.5 A: 6ES7132-4BD01-0AA0
• 2DO 24 VDC/2A ST: 6ES7132-4BB31-0AA0
• 2DO 24 VDC/2A HF: 6ES7132-4BB31-0AB0
• 4DO 24 VDC/2A ST: 6ES7132-4BD31-0AA0
• 2RO NO 24 ..120 VDC/5A 24 ..230 VAC/5A: 6ES7132-4HB01-0AB0
ET 200S
Operating Instructions, 12/2005, A5E00515771-03
Areas of application
From 0 to 60 °C
From 0 to 40 °C
From 0°C to 55/50 °C
(see restrictions below)*
10 K/h
From 15 to a maximum of 95%
from 1080 hPa to 795 hPa
SO
: < 0.5 ppm;
2
rel. humidity < 60 %, no condensation
H
S: < 0.1 ppm;
2
rel. humidity < 60 %, no condensation
General technical specifications
9.4 Mechanical and Climatic Ambient Conditions
Remarks
For horizontal installation
For all other mounting positions
For vertical installation
Without condensation
Corresponds to an altitude of -1000 m
to 2000 m
Test:
10 ppm; 4 days
1 ppm; 4 days
9-7