Siemens Simatic ET 200S Operating Instructions Manual page 338

Distributed i/o system
Hide thumbs Also See for Simatic ET 200S:
Table of Contents

Advertisement

Maintenance
If repair is necessary, the affected subassemblies/modules must be sent to the
production location. Repairs can only be carried out there.
Special Conditions
1. Subassemblies/modules must be installed in a cabinet or metal housing. These
must comply with the IP 54 degree of protection as a minimum. The
environmental conditions under which the equipment is installed must be taken
into account. There must be a manufacturer's declaration for zone 2 available
for the housing (in accordance with EN 50021).
2. If a temperature of > 70 °C is reached in the cable or at the cable entry of this
housing under operating conditions, or if a temperature of > 80 °C can be
reached at the junction of the conductors under operating conditions, the
temperature-related properties of the cables must correspond to the
temperatures actually measured.
3. The cable entries used must comply with the required IP degree of protection
and Section 7.2 (in accordance with EN 50021).
4. All devices (including switches, etc.) that are connected to the inputs and
outputs of SIMATIC systems must be approved for EEx nA or EEx nC explosion
protection.
5. Steps must be taken to ensure that the rated voltage through transients cannot
be exceeded by more than 40 %.
6. Ambient temperature range: 0° C to 60° C
7. A sign containing the following warning must be put up inside the housing in an
easily visible position when the housing is opened:
Warning
!
The housing can only be opened for a short time (e.g. for visual diagnostics). If
you do this, do not operate any switches, remove or install any modules or
disconnect any electrical cables (plug-in connections).
You can disregard this warning if you know that the atmosphere is not hazardous
(i.e. there is no risk of explosion).
List of Approved Subassemblies/Modules
You will find the list of approved subassemblies/modules under the ID 13702947
on the Internet:
http://www4.ad.siemens.de/view/cs/.
6
English
Product Information on the Use of subassemblies/modules in a Zone 2 Hazardous Area
A5E00352937-02

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents