Map 0200: Post Failure Analysis; Map 200 Event Codes - IBM TotalStorage SAN32M-2 Installation And Service Manual

Hide thumbs Also See for TotalStorage SAN32M-2:
Table of Contents

Advertisement

MAP 0200: POST failure analysis

Was the maintenance action successful?
NO
YES
The product is operational. Exit MAP.
6
Verify power supply operation.
a. Inspect each power supply to determine if the amber failure LED
is illuminated.
b. If an amber LED is illuminated, ensure the indicated power
supply is correctly installed and seated. Partially remove and
reseat the power supply. Refer to
Redundant power
Was the maintenance action successful?
NO
YES
The product is operational. Exit MAP.
A power supply failure is indicated. Go to
This MAP describes fault isolation for a POST failure. The failure
indicator is event code 400 or 411 observed at the Event Log (EFCM
Basic Edition or Element Manager interface).
1
Table 9
lists event codes, explanations, and MAP steps.

MAP 200 Event Codes

Table 9
Event
Explanation
code
400
Power-up diagnostic failure.
411
Firmware fault.
Field-replaceable unit:
supply.
step
Chapter 3: Maintenance analysis procedures
3.
Action
Go to
step
2.
Go to
step
4.
107