2.8.5
Connection of the multifunction regeneration
converter (FR-XC)
 Common bus regeneration mode with harmonic suppression disabled
(Pr.416 = "0")
When connecting the multifunction regeneration converter (FR-XC) to improve the braking capability, perform wiring securely
as follows. Incorrect connection will damage the converter and the inverter.
Turn ON switch 1 (connection mode setting switch) in the function selection switch assembly (SW2). If the switch setting does
not match the actual wiring, the connection mode fault "E.T" occurs.
After making sure that the wiring is correct and secure, set "2 or 102" in Pr.30 Regenerative function selection. (Refer to
page
566.)
MCCB MC
Fuse
Fuse
Power
supply
Fuse
*1
Never connect the power supply to terminals R/L1, S/L2, and T/L3 on the inverter. Incorrect connection will damage the inverter and the converter.
*2
Instead of connecting the terminals to the AC power supply, the control circuit can be powered by connecting terminal R1/L11 to terminal P/+ and
terminal S1/L21 to terminal N/-. In this case, do not connect the terminals to the AC power supply. Doing so will damage the inverter.
*3
When the FR-XC is connected, the jumper across terminals P/+ and P1 does not affect the function. (The FR-XC can be connected with the
jumper connected. Refer to
84
2. INSTALLATION AND WIRING
2.8 Connection of stand-alone option units
Downloaded from
ManualsNet.com
FR-XCL
*5*10
R/L1
R2/L12
R2/L12
*9
*9
S/L2
S2/L22
S2/L22
T/L3
T2/L32
T2/L32
*9
R/L1
*5*6
S/L2
*8
T/L3
R1/L11
S1/L21
RES
SOF
LOH
SD
page 50
for the jumper connection status in the initial setting.)
search engine
FR-XC
P4
*11
Junction terminal
P/+
Fuse
N/-
Fuse
RYB
RSO
SE
C
B
A
Junction terminal
Fuse
Fuse
Junction terminal
Fuse
Fuse
Inverter
U
*1
R/L1
V
S/L2
IM
M
W
T/L3
R1/L11
*2
S1/L21
P/+
*3*4
P1
N/-
X10(MRS)
*7
RES
SD
Inverter
*1
U
R/L1
V
S/L2
IM
M
W
T/L3
R1/L11
*2
S1/L21
P/+
*3*4
P1
N/-
X10(MRS)
*7
RES
SD
Inverter
*1
U
R/L1
V
S/L2
IM
M
W
T/L3
R1/L11
*2
S1/L21
P/+
*3*4
P1
N/-
X10(MRS)
*7
RES
SD