Mitsubishi Electric FR-F800 Series Instruction Manual page 211

Hide thumbs Also See for FR-F800 Series:

Advertisement

 Access to parameters according to the password status
Parameter
Read
Pr.296
Write
Read
Pr.297
Write
Pr.CLR write
(Parameter clear)
ALL.C All write
(All parameter
clear)
Pr.CPY write
(Parameter copy)
○: Enabled, ×: Disabled
*1
Reading/writing is disabled if reading is restricted by the Pr.160 setting. (Reading is available in the Network operation mode regardless of the
Pr.160 setting.)
*2
All parameter clear cannot be performed during the operation.
*3
Inputting a password is possible but the locked-up password cannot be unlocked or reset even with the valid password.
*4
Parameter clear can be performed only via a communication option.
NOTE
• When "4, 5, 104, or 105" is set in Pr.296 and a password is set, Pr.15 Jog frequency is not listed on the parameter unit (FR-
PU07).
• When a password has been set and parameters are locked, Parameter copy cannot be performed using the operation panel,
parameter unit, or a USB memory device .
Parameters referred to
Pr.77 Parameter write
Pr.160 User group read
Pr.550 NET mode operation command source
Pr.551 PU mode operation command source
5.4.15 Free parameter
Any number within the setting range of 0 to 9999 can be input.
For example, these numbers can be used:
• As a unit number when multiple units are used.
• As a pattern number for each operation application when multiple units are used.
• As the year and month of introduction or inspection.
Pr.
888
Free parameter 1
E420
889
Free parameter 2
E421
NOTE
• Pr.888 and Pr.889 do not influence the operation of the inverter.
210
5. PARAMETERS
5.4 (E) Environment setting parameters
Downloaded from
ManualsNet.com
Password protection disabled / Parameters
unlocked
Pr.296 = "9999",
Pr.297 = "9999"
*1
*1
*1
*1
×
selectionpage 206
selectionpage 215
selectionpage 251
selectionpage 251
Name
Initial value
9999
9999
search engine
Parameters locked
Pr.296 ≠ "9999",
Pr.296 ≠ "9999",
Pr.297 = "9999"
Pr.297 = "0 to 4" (read value)
×
*4
×
*2
×
Setting range
0 to 9999
Any value can be input.
The settings are retained even if the inverter power is turned
OFF.
0 to 9999
Password locked up
Pr.296 = "100 to 106, 199"
Pr.297 = "5" (read value)
×
*3
*4
×
*2
×
Description