2.6

Control circuit

2.6.1
Details on the control circuit terminals
 Input signal
Terminal
Type
Common
symbol
*1
STF
*1
STR
STP
*1
(STOP)
RH, RM,
*1
RL
*1
JOG
SD (sink
(negative
common))
PC
*1
RT
(source
(positive
common))
*1
MRS
*1
RES
*1
AU
*1
CS
60
2. INSTALLATION AND WIRING
2.6 Control circuit
Downloaded from
ManualsNet.com
Terminal name
Turn ON the STF signal to start
Forward rotation
forward rotation and turn it OFF to
start
stop.
Turn ON the STR signal to start
Reverse rotation
reverse rotation and turn it OFF to
start
stop.
Start self-holding
Turn ON the STP (STOP) signal to self-hold the start
selection
signal.
Multi-speed
Multi-speed can be selected according to the
selection
combination of RH, RM and RL signals.
Turn ON the JOG signal to enable JOG operation
Jog mode selection
(initial setting) and turn ON the start (STF or STR)
signal to start JOG operation.
Terminal JOG is also used as a pulse train input
terminal. To use as a pulse train input terminal, change
Pulse train input
the Pr.291 setting.
(Maximum input pulse: 100k pulses/s)
Turn ON the RT signal to enable the second function.
When the second function such as "Second torque
Second function
boost" and "Second V/F (base frequency)" is set,
selection
turning ON the RT signal enables the selected
function.
Turn ON the MRS signal (2 ms or more) to stop the
inverter output.
Output stop
Use this signal to shut off the inverter output when
stopping the motor with an electromagnetic brake.
Use this signal to reset a fault output provided when a
protective function is activated.
Turn ON the RES signal for 0.1 second or longer, then
turn it OFF.
Reset
In the initial setting, reset is always enabled. By setting
Pr.75, reset can be enabled only at an inverter fault
occurrence. The inverter recovers about 1 second after
the reset is released.
The terminal 4 function is available only when the AU
Terminal 4 input
signal is ON.
selection
Turning the AU signal ON makes terminal 2 invalid.
Use Pr.186 CS terminal function selection for
(No function)
function assignment.
search engine
Terminal function description
When the STF
and STR signals
are turned ON
simultaneously,
the stop
command is
given.
Refer
Rated specification
to
page
563
Input resistance: 4.7
kΩ, voltage when
contacts are open: 21
to 27 VDC, current
563
when contacts are
short-circuited: 4 to 6
mADC
263
261
Input resistance: 2 kΩ,
current when contacts
258
are short-circuited: 8 to
13 mADC
377
375
Input resistance: 4.7
kΩ, voltage when
contacts are open: 21
to 27 VDC, current
when contacts are
short-circuited: 4 to 6
196
mADC
349