6.6
Check first when you have a trouble
• If the cause is still unknown after every check, it is recommended to initialize the parameters, set the required parameter values
and check again.
6.6.1
Motor does not start
Check
point
An appropriate power supply voltage is not
applied.
(The operation panel display is not
operating.)
Main
circuit
The motor is not connected properly.
The jumper across P/+ to P1 is
disconnected.
A DC reactor (FR-HEL) is not connected.
612
6. PROTECTIVE FUNCTIONS
6.6 Check first when you have a trouble
Downloaded from
ManualsNet.com
Possible cause
search engine
Countermeasure
Power on a molded case circuit breaker (MCCB), an earth leakage
circuit breaker (ELB), or a magnetic contactor (MC).
Check for the decreased input voltage, input phase loss, and
wiring.
If only the control power is ON when using a separate power
source for the control circuit, turn ON the main circuit power.
Check the wiring between the inverter and the motor.
If the electronic bypass function is active, check the wiring of the
magnetic contactor (MC) between the inverter and the motor.
Securely fit a jumper across P/+ and P1.
When using a DC reactor (FR-HEL), remove the jumper across P/
+ to P1, and then connect the DC reactor.
Connect the DC reactor securely when required according to the
capacity.
Refer to
page
69
50
50,
88