 Soft-PWM control (Pr.240)
• Soft-PWM control is a function that changes the motor noise from a metallic sound into an inoffensive, complex tone.
• Setting Pr.240 = "1" will enable the Soft-PWM control.
• To enable the Soft-PWM control, set Pr.72 to 5 kHz or less for the FR-F820-02330(55K) or lower or the FR-F840-
01160(55K) or lower. For the FR-F820-03160(75K) or higher or the FR-F840-01800(75K) or higher, set Pr.72 to 4 kHz or
less.
NOTE
• While a sine wave filter (Pr.72 = "25") is being used, the Soft-PWM control is disabled.
 PWM carrier frequency automatic reduction function (Pr.260)
• Setting Pr.260 = "1 (initial value)" will enable the PWM carrier frequency auto-reduction function. If a heavy load is
continuously applied while the inverter carrier frequency is set to 3 kHz or higher (Pr.72 ≥ "3"), the carrier frequency is
automatically reduced to prevent occurrence of the Inverter overload trip (electronic thermal relay function) (E.THT). The
carrier frequency is reduced to as low as 2 kHz. Motor noise increases, but not to the point of failure.
• When the carrier frequency automatic reduction function is used, operation with the carrier frequency set to 3 kHz or higher
(Pr.72 ≥ 3) automatically reduces the carrier frequency for heavy-load operation as shown below.
Pr.260
setting
1
0
NOTE
• Reducing the PWM carrier frequency is effective as a countermeasure against EMI from the inverter or for reducing leakage
current, but doing so increases the motor noise.
• When the PWM carrier frequency is set to 1 kHz or lower (Pr.72 ≤ 1), the increase in the harmonic current causes the fast-
response current limit to activate before the stall prevention operation, which may result in torque shortage. In this case,
disable the fast-response current limit in Pr.156 Stall prevention operation selection.
Parameters referred to
Pr.156 Stall prevention operation
Pr.570 Multiple rating
Pr.800 Control method
Downloaded from
ManualsNet.com
Pr.570 setting
The carrier frequency will reduce automatically with continuous operation of 85% of the inverter rated
0 (SLD), 1 (LD)
current or higher.
The carrier frequency will reduce automatically with continuous operation of 85% of the inverter rated
0 (SLD)
current or higher.
Without carrier frequency automatic reduction (Perform continuous operation with the carrier frequency
1 (LD)
set to 2 kHz or lower or with less than 85% of the inverter rated current.)
selectionpage 290
settingpage 204
selectionpage 177
search engine
Carrier frequency automatic reduction operation
5. PARAMETERS
5.4 (E) Environment setting parameters
1
2
3
4
5
6
7
8
9
10
219