5.4.14 Password
Registering a 4-digit password can restrict access to parameters (reading/writing).
Pr.
296
Password lock level
E410
297
Password lock/unlock
E411
These parameters can be set when Pr.160 User group read selection = "0". However, when Pr.296 ≠ 9999 (Password
protection enabled), Pr.297 can always be set, regardless of the setting in Pr.160.
*1
Although "0 or 9999" can be input in Pr.297, the value is invalid. (The display cannot be changed.)
 Parameter reading/writing restriction level (Pr.296)
• The access (reading/writing) restriction level to parameters in the PU operation mode or NET operation mode can be
selected with Pr.296.
Pr.296 setting
9999
*6
0, 100
1, 101
2, 102
3, 103
4, 104
5, 105
6, 106
99, 199
○: Enabled, ×: Disabled
*1
If the parameter reading is restricted by the setting of Pr.160 User group read selection, those parameters cannot be read even when "○" is
indicated.
*2
If the parameter writing is restricted by the setting of Pr.77 Parameter write selection, those parameters cannot be written even when "○" is
indicated.
*3
Access from the command source in the PU operation mode (the operation panel (FR-DU08) or the parameter unit in the initial setting) is
restricted. (For the PU operation mode command source selection, refer to
*4
Access from the command source in the Network operation mode (the RS-485 terminals or a communication option in the initial setting) is
restricted. (For the NET operation mode command source selection, refer to
*5
Read/write is enabled only for the simple mode parameters registered in the user group when Pr.160 = "9999". Pr.296 and Pr.297 can be read
or written regardless of whether they are registered to the user group.
*6
If a communication option is installed, the Option fault (E.OPT) occurs, and the inverter output shuts off. (Refer to
*7
The PLC function user parameters (Pr.1150 to Pr.1199) can be written and read by the PLC function regardless of the Pr.296 setting.
208
5. PARAMETERS
5.4 (E) Environment setting parameters
Downloaded from
ManualsNet.com
Name
Initial value
9999
9999
Access to parameters in the PU
*3
operation mode
*1
*2
Read
Write
×
×
×
×
×
×
×
×
Only the parameters registered in the user group can be read/written (For the parameters not registered in the user
group, the restriction level when "4 or 104" is set applies.).
search engine
Setting range
Password protection enabled. Setting the access
0 to 6, 99, 100,
(reading/writing) restriction level to parameters locked
106, 199
with a password enables writing to Pr.297.
9999
No password protection
Input a 4-digit password to lock parameters, or input the
1000 to 9998
valid password to unlock the locked parameters.
Number of failed password attempts (read only,
*1
displayed after any of "100 to 106, or 199" is set in
(0 to 5)
Pr.296 and a password to lock parameters is input).
*1
No password protection
9999
Access to parameters in the NET operation mode
via RS-485 terminals / using PLC
*7
function
*2
Read
Write
×
×
×
×
×
×
×
×
*5
page
251.)
page
251.)
Description
*4
via communication option
*2
Read
Write
×
×
×
×
×
×
page
605.)