Download Print this page

Mitsubishi Electric FR-F800 Series Instruction Manual page 413

Hide thumbs Also See for FR-F800 Series:

Advertisement

• When the protective function of the inverter is activated, the MC1 signal is immediately turned OFF according to the Pr.248
setting. (The MC1 signal is turned OFF before the time set in Pr.254 has passed.)
When Pr.248 = "1", the MC1 signal is turned OFF when the protective function is activated due to any cause.
When Pr.248 = "2", the MC1 signal is turned OFF only when the protective function is activated due to an error resulted
from a failure in the inverter circuit or a wiring error (refer to the following table). (For the fault details, refer to
Inrush current limit circuit fault (E.IOH)
CPU fault (E.CPU)
CPU fault (E.6)
CPU fault (E.7)
Parameter storage device fault (control circuit board) (E.PE)
Parameter storage device fault (main circuit board) (E.PE2)
Internal storage device fault (E.PE6)
24 VDC power fault (E.P24)
Operation panel power supply short circuit/RS-485 terminals power supply short circuit
(E.CTE)
Output side earth (ground) fault overcurrent (E.GF)
Output phase loss (E.LF)
Internal circuit fault (E.BE)
Internal circuit fault (E.13/E.PBT)
• To enable the self power management function for the separated converter type, enable the self power management
function also on the converter unit side. To activate the self power management function when a converter unit fault occurs,
connect the terminal to which the Y17 signal of the converter unit is assigned and the terminal to which X94 signal of the
inverter is assigned.
Y17 output signal
(on the converter unit side)
OFF
OFF
ON
ON
• To use the X94 signal, set "94" in any parameter from Pr.178 to Pr.189 (Input terminal function selection) to assign the
function to an input terminal.
412
5. PARAMETERS
5.11 (A) Application parameters
Downloaded from
ManualsNet.com
Fault type
MC1 output signal
(inverter side)
OFF
ON
OFF
ON
search engine
MC1 output signal actual
operation
OFF
OFF
OFF
ON
page
594.)
Main circuit power supply
Stop
Stop
Stop
Supplied

Advertisement

loading