• Starting conditions of the timer for a time trigger
When the start command turns ON
When the cleaning ends
STF
Y215
Output
frequency
0 Hz
 Cleaning operation by the cleaning signal (X97 signal)
• When X97 signal is assigned to an input terminal, the cleaning operation can be finished when the cleaning signal (X97)
is turned from ON to OFF.
• For the X97 signal input, set "97" in any parameter from Pr.178 to Pr.189 to assign the function.
Pr.1470 setting
0
Other than 0
NOTE
• When a trigger occurs during the following operations, the cleaning operation is started upon completion of the following
operations.
Automatic restart after instantaneous power failure, online auto tuning at startup
• The following functions are disabled during cleaning operation.
PID control automatic switchover frequency, PID control sleep function, pre-charge fault, determination of pre-charge ending
with parameters, PID gain tuning, switchover to the commercial power supply operation with the automatic switchover
frequency of the inverter (Pr.139), automatic switchover of auxiliary motors of the multi-pump function, output stop function
(Pr.522), restart at every start during cleaning
• When the stall prevention is activated during acceleration of the cleaning function, the operation is shifted to the cleaning
deceleration operation.
• If the number of cleaning times set in Pr.1470 is an even number, the operation is shifted to the normal operation after the
cleaning forward/reverse operation time (Pr.1473/Pr.1475) of the final cleaning operation has elapsed.
• Changing the terminal assignment with Pr.178 to Pr.189 and Pr.190 to Pr.196 may affect other functions. Set parameters
after confirming the function of each terminal.
Parameters referred to
Pr.178 to Pr.189 (Input terminal function
Pr.190 to Pr.196 (Output terminal function
Pr.7 Acceleration time, Pr.8 Deceleration
418
5. PARAMETERS
5.11 (A) Application parameters
Downloaded from
ManualsNet.com
ON
Start command ON trigger
ON
Pr.1479
Cleaning
Normal
operation
operation
(Pr.1470 = Once)
X97 signal
Assignment
ON/OFF
Optional
Optional
Not assigned
OFF
Assigned
ON
selection)page 373
selection)page 330
timepage 228
search engine
Time trigger
Time trigger
ON
ON
Pr.1479
Cleaning
Normal
operation
operation
(Pr.1470 = Once)
(Pr.1470 = Once)
Cleaning operation
Disabled
Enabled
Disabled
Enabled
Time
Cleaning
Normal
operation
operation
Cleaning end condition
After cleaning is performed for the
number of times set in Pr.1470.
• After cleaning is performed for the
number of times set in Pr.1470.
• When X97 signal turns OFF.