 Calibration of terminal AM (C1 (Pr.901))
• Terminal AM is initially set to provide a 10 VDC output in the full-scale state of the corresponding monitor item. The
calibration parameter C1 (Pr.901) AM terminal calibration allows the output voltage ratio (gains) to be adjusted according
to the meter scale. Note that the maximum output voltage is 10 VDC.
Inverter
AM
5
• Calibrate the output via terminal AM in the following procedure.
1.
Connect a 0-10 VDC indicator (frequency meter) across terminal AM and terminal 5 on the inverter. (Note the
polarity. Terminal AM is positive.)
2.
Set a monitor item in Pr.158 AM terminal function selection. (Refer to
When the output frequency or inverter output current is selected on the monitor, set the output frequency or current
value at which the output signal is 10 V, using Pr.55 or Pr.56 beforehand.
3.
If the meter needle does not point to maximum even at maximum output, calibrate it with C1 (Pr.901).
NOTE
• When outputting an item such as the output current, which cannot reach a 100% value easily by operation, set Pr.158 to "21"
(reference voltage output) and calibrate. A voltage of 10 VDC is output via terminal AM.
• When Pr.306 Analog output signal selection = "21", the output via terminal AM cannot be calibrated. For details on Pr.306,
refer to the Instruction Manual of the FR-A8AY.
• Use Pr.290 Monitor negative output selection to enable negative signals output via terminal AM. The output voltage range
is -10 to +10 VDC. Calibrate the maximum positive value output via terminal AM.
 Adjusting the response of terminal AM (Pr.867)
• Use Pr.867 to adjust the output voltage response of the terminal AM in the range of 0 to 5 seconds.
• Increasing the setting stabilizes the output via terminal AM more but reduces the response level. (Setting "0" means the
setting of the response level to 7 ms.)
Parameters referred to
Pr.54 FM/CA terminal function
Pr.55 Frequency monitoring
Pr.56 Current monitoring
Pr.158 AM terminal function
Pr.290 Monitor negative output
Pr.291 Pulse train I/O
Downloaded from
ManualsNet.com
10VDC
selectionpage 314
referencepage 314
referencepage 314
selectionpage 314
selectionpage 314
selectionpage 258
search engine
page
314.)
5. PARAMETERS
5.8 (M) Item and output signal for monitoring
1
2
3
4
5
6
7
8
9
10
323

Advertisement

loading