 Multi-pump function control method
• Use Pr.579 Motor connection function selection to select the control method for the multi-pump function. Use Pr.578
Auxiliary motor operation selection to set the number of auxiliary motors.
Pr.579 setting
0
1
2
3
Pr. 579 = 0
Pr. 579 = 1
Pr. 579 = 2
Pr. 579 = 3
*1
The starting order of motors is M2-M3-M1 if the previous order was M1-M2-M3.
*2
The motor starts in the order of elapsed time after completion of the previous inverter-driven operation, from the longest to the shortest. (The
motor that has not been driven by the inverter for the longest time starts first.)
Downloaded from
ManualsNet.com
Control method
The motor driven by the inverter is always fixed. Commercial power supply operation of auxiliary
Basic system
motors is available by turning ON and OFF the MC between the power supply and the motor
depending on the output frequency of the inverter.
The motor driven by the inverter is fixed during operation. Commercial power supply operation of
auxiliary motors is available by turning ON and OFF the MC between the power supply and the
Alternative system
motor depending on the output frequency of the inverter.
When output is shut off by the sleep function, the MC between the inverter and the motor is
switched to switch the motor to be driven by the inverter.
When the start signal is turned ON, the motor is started by the inverter. When the conditions to
start the next motor are established, MCs between the inverter and the motor and the power
supply and the motor are switched to change the operation of the motor driven by the inverter to
Direct system
commercial power supply operation, and the next motor is started by the inverter.
When conditions to stop motors are established while auxiliary motors are running, the motor
started first (currently driven by the commercial power supply) is stopped first, and then the other
motors are stopped.
When the start signal is turned ON, the motor is started by the inverter. When the conditions to
start the next motor are established, MCs between the inverter and the motor and the power
supply and the motor are switched to change the operation of the motor driven by the inverter to
commercial power supply operation, and the next motor is started by the inverter.
Alternative direct
When conditions to stop motors are established while auxiliary motors are running, the motor
system
driven by the inverter is decelerated to stop, and operation of a motor currently driven by the
commercial power supply is switched to the inverter-driven operation after frequency search. To
perform frequency search when the motor operation is switched from commercial power supply
operation to inverter-driven operation, set Pr.57 Restart coasting time ≠ "9999".
Flow rateQ
Qmax
Q3
Q2
Q1
Motor 1 (M1)
Motor 2 (M2)
Motor 3 (M3)
Motor 4 (M4)
∗1
Motor 1 (M1)
Motor 2 (M2)
Motor 3 (M3)
Motor 4 (M4)
Motor 1 (M1)
Motor 2 (M2)
Motor 3 (M3)
Motor 4 (M4)
∗2
Motor 1 (M1)
Motor 2 (M2)
Motor 3 (M3)
Motor 4 (M4)
search engine
Description
Time
∗1
∗2
Driven
by inverter
Driven by
commercial
power supply
Stop