5. PARAMETERS
5.8 (M) Item and output signal for monitoring
Downloaded from
ManualsNet.com
Signal
Function
name
Inverter running and start
RUN3
command ON
During deceleration at
Y46
occurrence of power failure
PID
During PID control activated
Y48
PID deviation limit
Y49
During pre-charge operation
During second pre-charge
Y50
operation
Y51
Pre-charge time over
Y52
Second pre-charge time over
Y53
Pre-charge level over
Y54
Second pre-charge level over
IPM
PM motor control
Y64
During retry
Emergency drive in
Y65
*2
operation
Fault output during emergency
ALM3
*2
drive
*3
Y67
Power failed
24 V external power supply
EV
operation
SLEEP
PID output interruption
Commercial power supply side
RO1
motor 1 connection RO1
Commercial power supply side
RO2
motor 1 connection RO2
Commercial power supply side
RO3
motor 1 connection RO3
Commercial power supply side
RO4
motor 1 connection RO4
Inverter side motor 1
RIO1
connection RIO1
Inverter side motor 1
RIO2
connection RIO2
Inverter side motor 1
RIO3
connection RIO3
Inverter side motor 1
RIO4
connection RIO4
Pulse train output of output
Y79
power
SAFE
Safety monitor output
Y82
BACnet binary output
*2
Y85
DC current feeding
search engine
Operation
The signal is ON while the inverter is running
or while the start command signal is ON.
Output when the power-failure deceleration
function is activated.
(The signal output is retained until the
function stops.)
Output during the PID control operation.
Output when the absolute deviation value
exceeds the limit value.
Output while the pre-charge function is
working.
Output when the time period while the pre-
charge function is working reaches the time
limit set in Pr.764 or Pr.769.
Output when the value higher than the
detection level set in Pr.763 or Pr.768 is
measured until the pre-charge function stops
during pre-charge operation.
Output while the operation is performed
under PM motor control.
Output during retry operation.
Output during emergency drive operation.
Output when a fault occurs during emergency
drive operation.
Output when the inverter power output is shut
off due to power failure or undervoltage or
when the power failure time deceleration-to-
stop function is activated.
Output while the inverter operated with a 24
V power supplied from an external source.
Output while PID output suspension function
is activated.
Output depending on the motor drive
conditions when the multi-pump function is
used.
Output in pulses every time the cumulative
value of energy output from the inverter
reaches the Pr.799 setting.
Output while the safety stop function is
activated.
Enables output from the Binary Output object
for BACnet communication.
Output during power failure or undervoltage
of the AC power supply.
Refer
Related
to
parameter
page
335
Pr.261 to Pr.266
478
Pr.127 to Pr.134,
419
Pr.575 to Pr.577
Pr.127 to Pr.134,
419
Pr.553, Pr.554
Pr.127 to Pr.134,
Pr.241, Pr.553,
Pr.554, Pr.575 to
445
Pr.577, Pr.753 to
Pr.769, C42, C45
Pr.71 to Pr.80,
182
Pr.998
Pr.65 to Pr.69
276
Pr.514, Pr.515,
Pr.523, Pr.524,
279
Pr.1013
Pr.261 to Pr.266
478
73
Pr.127 to Pr.134,
419
Pr.575 to Pr.577
Pr.575 to Pr.591
450
Pr.799
346
74
Pr.549
533
Pr.30
566