 Locking parameters with a password (Pr.296, Pr.297)
• The procedure of locking parameters with a password is as follows.
1.
Set the parameter reading/writing restriction level to enable the password protection. (Set a value other than "9999"
in Pr.296.)
Pr.296 setting
0 to 6 or 99
100 to 106 or 199
*1
If an invalid password is input 5 times while any of "100 to 106, or 199" is set in Pr.296, the password is locked up afterward (the locked parameters
cannot be unlocked even with the valid password). All parameter clear is required to reset the password. (After All parameter clear is performed,
the parameters are returned to their initial values.)
2.
Write a four-digit number (1000 to 9998) to Pr.297 as a password (writing is disabled when Pr.296 = "9999"). After
a password is set, parameters are locked and access (reading/writing) to the parameters is limited at the level set
in Pr.296 until the valid password is input to unlock the locked parameters.
NOTE
• After a password is set, the Pr.297 readout is always any of "0 to 5".
• "
• Even if a password is set, the parameters which are written by the inverter, such as parameters related to the life check of
inverter parts, are overwritten as needed.
• Even if a password is set, Pr.991 PU contrast adjustment can be read/written when the parameter unit (FR-PU07) is
connected.
 Unlocking the locked parameters (Pr.296, Pr.297)
• There are two ways to unlock the locked parameters.
• Enter the password in Pr.297. When a valid password is input, the locked parameters can be unlocked. When an invalid
password is input, an error indication appears and the parameters cannot be unlocked. If an invalid password is input 5
times while any of "100 to 106, or 199" is set in Pr.296, the locked parameters cannot be unlocked afterward even with the
valid password (the password is locked up).
• Perform All parameter clear.
NOTE
• If the password is forgotten, it can be reset by performing All parameter clear, but the other parameters are also reset.
• All parameter clear cannot be performed during the inverter operation.
• When using FR Configurator2 in the PU operation mode, do not set "0, 4, 5, 99, 100, 104, 105, or 199" (parameter read is
disabled) in Pr.296. Doing so may cause abnormal operation.
• The means to reset the password varies according to how the reset command is sent (from the PU, through RS-485
communication, or via a communication option).
○: Password reset enabled, ×: Password reset disabled
• For the information how to perform Parameter clear or All parameter clear with the parameter unit or via a communication
option, refer to the Instruction Manual of the parameter unit or the option. (For the operation panel (FR-DU08), refer to
578. For RS-485 communication using the Mitsubishi inverter protocol, refer to
the MODBUS-RTU communication protocol, refer to
Downloaded from
ManualsNet.com
Allowable number of failed password
attempts
Unlimited
*1
Limited to 5 times
" appears when a password-protected parameter is attempted to be read/written.
All parameter clear
Parameter clear
search engine
Always 0
Number of failed password attempts (0 to 5)
PU (operation panel or
parameter unit)
communication
×
×
page
520.)
Pr.297 readout
RS-485
Communication
option
page
507. For RS-485 communication using