5.6.6
The frequency and acceleration/deceleration time for JOG operation can be set. JOG operation is possible in both External
operation and PU.
JOG operation can be used for conveyor positioning, test operation, etc.
Pr.
15
Jog frequency
D200
16
Jog acceleration/
F002
deceleration time
Note that these parameters are categorized as a simple mode parameter when the LCD operation panel (FR-LU08) or the
parameter unit (FR-PU07) is used. Setting of this parameter is enabled when the operation panel (FR-DU08) is connected and
"0" is set to Pr.160 User group read selection. (Refer to
*1
The Pr.20 initial value is set to 60 Hz for the FM type and to 50 Hz for the CA type.
 JOG operation using the external signals
• Operation can be started and stopped by the start signals (STF and STR signals) when the Jog operation selection (JOG)
signal is ON. (For the operation method, refer to
• While the JOGF or JOGR signal is input, Jog frequency setting (Pr.15) is used for operation. The rotation is forward while
the JOGF signal is input, and the rotation is reverse while the JOGR signal is input. (Direct JOG function)
• Use the JOG acceleration/deceleration time function (Pr.16) to set the acceleration/deceleration time for JOG operation.
• To use each signal, set the corresponding number selected from the following table in any parameter from Pr.178 to
Pr.189 (Input terminal function selection) to assign the function to an output terminal.
Input signal
JOG
JOGF
JOGR
Output frequency(Hz)
setting range
Forward rotation STF
Reverse rotation STR
 JOG operation using the PU
• When the operation panel or parameter unit is in the JOG operation mode, the motor jogs only while the start button is
pressed. (For the operation method, refer to
Downloaded from
ManualsNet.com
JOG operation
Initial
Name
value
5 Hz
0 to 590 Hz
0.5 s
0 to 3600 s
Pr.178 to Pr.189 settings
5 (Pr.185 initial value)
57
58
Pr.20
Pr.15
Forward
rotation
Pr.16
JOG signal
ON
ON
ON
search engine
Setting range
Set the frequency for JOG operation.
Set the motor acceleration/deceleration time during JOG operation.
For the acceleration/deceleration time, set the time until the
frequency
frequency is reached.
The acceleration/deceleration times cannot be set separately.
page
215.)
page
136.)
Output frequency(Hz)
Pr.20
Pr.15
setting range
Time
Reverse
rotation
JOGF signal
JOGR signal
page
137.)
Description
*1
set in Pr.20 Acceleration/deceleration reference
Forward
rotation
Reverse
rotation
Pr.16
ON
ON
5.6 (D) Operation command and frequency command
1
2
3
4
5
6
7
8
9
10
Time
261
5. PARAMETERS