Download Print this page

Mitsubishi Electric FR-F800 Series Instruction Manual page 666

Hide thumbs Also See for FR-F800 Series:

Advertisement

• When the inverter is used in an environment with the surrounding air temperature exceeding 40°C, the rated output current
must not exceed the value shown in the following table.
Inverter model
FR-F846-[]-C2
00023(0.75K)
00038(1.5K)
00052(2.2K)
00083(3.7K)
00126(5.5K)
00170(7.5K)
00250(11K)
00310(15K)
00380(18.5K)
00470(22K)
00620(30K)
00770(37K)
00930(45K)
01160(55K)
01800(75K)
02160(90K)
02600(110K)
03250(132K)
03610(160K)
 Example of installing ferrite cores
Ferrite core
• The wiring must be contained in the casing.
• When there is more than one bundle of control signal lines, install ferrite cores to each bundle.
 Recommended ferrite core
Manufacturer: TOKIN Corporation
Model: ESD-SR-250
φ13.0 or less
(Unit: mm)
For details on this ferrite core, contact TOKIN Corporation.
Downloaded from
ManualsNet.com
Rated output current
Surrounding air
temperature: 45°C
2.0 A
3.3 A
4.6 A
7.2 A
10.9 A
13.6 A
22 A
28 A
33 A
37 A
54 A
67 A
81 A
101 A
137 A
171 A
205 A
247 A
284 A
Control cable
For using one ferrite core
31.5
search engine
Surrounding air
temperature: 50°C
1.9 A
3.2 A
4.3 A
6.8 A
9.2 A
11.2 A
21 A
26 A
28 A
30.1 A
51 A
63 A
77 A
95 A
130 A
162 A
178 A
234 A
244 A
For using two ferrite cores
38.0
9.3 Acquisition of type certification for ship classification standards (400 V class)
1
2
3
4
5
6
7
8
9
10
665
9. APPENDIX

Advertisement