5.9.1
The functions to switch the analog input terminal specifications, override function, forward/reverse rotation by the input signal
polarity are selectable.
Pr.
73
Analog input selection
T000
267
Terminal 4 input
T001
selection
 Analog input specification selection
• For terminals 2 and 4 used for analog input, the voltage input (0 to 5 V, 0 to 10 V) and current input (0 to 20 mA) are
selectable. To change the input specification, change the setting of Pr.73 (Pr.267) and the voltage/current input selection
switch (switch 1 or switch 2).
Voltage/current
input switch
Switch 2
Switch 1
2
Switch state
ON
Switch 1
OFF
ON
Switch 2
OFF
• Change the setting of the voltage/current input selection switch to change the rated specification of terminal 2 or 4.
• Set Pr.73 (Pr.267) and the voltage/current input selection switch according to the analog signal input. The incorrect
settings shown in the following table cause a failure. The inverter does not operate properly with other incorrect settings.
Setting causing a failure
Switch setting
ON (Current input)
OFF (Voltage input) Current input
NOTE
• Check the number of the voltage/current input selection switch before setting, because it is different from the switch number
indicated on the FR-F700(P) series inverter.
Downloaded from
ManualsNet.com
Analog input selection
Name
Initial value
1
0
4
Input specification
Current input
Voltage input (initial status)
Current input (initial status)
Voltage input
Terminal input
Causes an analog signal output circuit failure in an external device (due to increased loads on the
Voltage input
signal output circuit of the external device).
Causes an input circuit failure in the inverter (due to an increased output power in the analog signal
output circuit of an external device).
search engine
Setting
range
0 to 5, 10
Switch 1 - OFF
to 15
(initial status)
6 to 7, 16,
Switch 1 - ON
17
Switch 2 - ON
0
(initial status)
1
Switch 2 - OFF
2
Input
terminal
For voltage input, the input resistance is 10 ±1 kΩ and the
Terminal 2
maximum permissible voltage is 20 VDC.
For current input, the input resistance is 245 ±5 Ω and the
Terminal 4
maximum permissible current is 30 mA.
Description
The terminal 2 input specification (0 to 5 V, 0 to 10
V, 0 to 20 mA) and terminal 1 input specification (0
to ±5 V, 0 to ±10 V) are selectable. Also the
override and reversible operation settings are
selectable.
Terminal 4 input, 4 to 20 mA
Terminal 4 input, 0 to 5 V
Terminal 4 input, 0 to 10 V
Rated specification
Operation
5.9 (T) Multi-function input terminal parameters
1
2
3
4
5
6
7
8
9
10
349
5. PARAMETERS

Advertisement